CVE-2011-4033 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2025-04-11 N/A
Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to cause a denial of service via unspecified vectors.
CVE-2011-4034 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2025-04-11 N/A
Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to execute arbitrary code or cause a denial of service via unspecified vectors.
CVE-2011-3143 2 Aveva, Schneider-electric 3 Clearscada, Scx 67, Scx 68 2025-04-11 N/A
Use-after-free vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via unspecified long strings that trigger heap memory corruption.
CVE-2011-3144 2 Aveva, Schneider-electric 3 Clearscada, Scx 67, Scx 68 2025-04-11 N/A
Cross-site scripting (XSS) vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2011-4859 1 Schneider-electric 21 M340 Ethernet Module Bmxnoe0100, M340 Ethernet Module Bmxnoe0110, M340 Ethernet Module Bmxp342020 and 18 more 2025-04-11 N/A
The Schneider Electric Quantum Ethernet Module, as used in the Quantum 140NOE771* and 140CPU65* modules, the Premium TSXETY* and TSXP57* modules, the M340 BMXNOE01* and BMXP3420* modules, and the STB DIO STBNIC2212 and STBNIP2* modules, uses hardcoded passwords for the (1) AUTCSE, (2) AUT_CSE, (3) fdrusers, (4) ftpuser, (5) loader, (6) nic2212, (7) nimrohs2212, (8) nip2212, (9) noe77111_v500, (10) ntpupdate, (11) pcfactory, (12) sysdiag, (13) target, (14) test, (15) USER, and (16) webserver accounts, which makes it easier for remote attackers to obtain access via the (a) TELNET, (b) Windriver Debug, or (c) FTP port.
CVE-2013-6143 1 Schneider-electric 1 Telvent Sage 3030 Firmware 2025-04-11 N/A
The Schneider Electric Telvent SAGE 3030 RTU with firmware C3413-500-001D3_P4 and C3413-500-001F0_PB allows remote attackers to cause a denial of service (temporary outage and CPU consumption) via malformed DNP3 traffic.
CVE-2013-2761 1 Schneider-electric 1 Modicon M340 2025-04-11 N/A
The Schneider Electric M340 BMXNOE01xx and BMXP3420xx PLC modules allow remote authenticated users to cause a denial of service (module crash) via crafted FTP traffic, as demonstrated by the FileZilla FTP client.
CVE-2013-2762 1 Schneider-electric 1 Magelis Xbt Hmi 2025-04-11 N/A
The Schneider Electric Magelis XBT HMI controller has a default password for authentication of configuration uploads, which makes it easier for remote attackers to bypass intended access restrictions via crafted configuration data.
CVE-2013-2763 1 Schneider-electric 24 Modicon M340 Bmx Noc 0401, Modicon M340 Bmx Noc 0401 Firmware, Modicon M340 Bmx Noe 0100 and 21 more 2025-04-11 N/A
The Schneider Electric M340 PLC modules allow remote attackers to cause a denial of service (resource consumption) via unspecified vectors. NOTE: the vendor reportedly disputes this issue because it "could not be duplicated" and "an attacker could not remotely exploit this observed behavior to deny PLC control functions.
CVE-2013-0655 1 Schneider-electric 1 Software Update Utility 2025-04-11 N/A
The client in Schneider Electric Software Update (SESU) Utility 1.0.x and 1.1.x does not ensure that updates have a valid origin, which allows man-in-the-middle attackers to spoof updates, and consequently execute arbitrary code, by modifying the data stream on TCP port 80.
CVE-2013-0663 1 Schneider-electric 3 Modicon M340, Modicon Premium, Modicon Quantum Plc 2025-04-11 N/A
Cross-site request forgery (CSRF) vulnerability on the Schneider Electric Quantum 140NOE77111, 140NOE77101, and 140NWM10000; M340 BMXNOC0401, BMXNOE0100x, and BMXNOE011xx; and Premium TSXETY4103, TSXETY5103, and TSXWMY100 PLC modules allows remote attackers to hijack the authentication of arbitrary users for requests that execute commands, as demonstrated by modifying HTTP credentials.
CVE-2013-0664 1 Schneider-electric 3 Modicon M340, Modicon Premium, Modicon Quantum Plc 2025-04-11 N/A
The FactoryCast service on the Schneider Electric Quantum 140NOE77111 and 140NWM10000, M340 BMXNOE0110x, and Premium TSXETY5103 PLC modules allows remote authenticated users to send Modbus messages, and consequently execute arbitrary code, by embedding these messages in SOAP HTTP POST requests.
CVE-2013-0687 1 Schneider-electric 1 Micom S1 Studio 2025-04-11 N/A
The installer routine in Schneider Electric MiCOM S1 Studio uses world-writable permissions for executable files, which allows local users to modify the service or the configuration files, and consequently gain privileges or trigger incorrect protective-relay operation, via a Trojan horse executable file.
CVE-2012-0931 1 Schneider-electric 1 Modicon Quantum Plc 2025-04-11 9.8 Critical
Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors.
CVE-2011-4035 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2025-04-11 N/A
Cross-site scripting (XSS) vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2011-4036 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2025-04-11 N/A
Directory traversal vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to read arbitrary files via unspecified vectors.
CVE-2023-3001 1 Schneider-electric 1 Igss Dashboard 2025-03-05 7.8 High
A CWE-502: Deserialization of Untrusted Data vulnerability exists in the Dashboard module that could cause an interpretation of malicious payload data, potentially leading to remote code execution when an attacker gets the user to open a malicious file.
CVE-2022-34755 1 Schneider-electric 1 Easergy Builder Installer 2025-03-03 6.3 Medium
A CWE-427 - Uncontrolled Search Path Element vulnerability exists that could allow an attacker with a local privileged account to place a specially crafted file on the target machine, which may give the attacker the ability to execute arbitrary code during the installation process initiated by a valid user. Affected Products: Easergy Builder Installer (1.7.23 and prior)
CVE-2023-25548 1 Schneider-electric 1 Struxureware Data Center Expert 2025-03-03 8.8 High
A CWE-863: Incorrect Authorization vulnerability exists that could allow access to device credentials on specific DCE endpoints not being properly secured when a hacker is using a low privileged user. Affected products: StruxureWare Data Center Expert (V7.9.2 and prior)
CVE-2023-25552 1 Schneider-electric 1 Struxureware Data Center Expert 2025-03-03 8.1 High
A CWE-862: Missing Authorization vulnerability exists that could allow viewing of unauthorized content, changes or deleting of content, or performing unauthorized functions when tampering the Device File Transfer settings on DCE endpoints. Affected products: StruxureWare Data Center Expert (V7.9.2 and prior)