| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| A security issue exists in FactoryTalk ViewPoint version 14.0 or below due to improper handling of MSI repair operations. During a repair, attackers can hijack the cscript.exe console window, which runs with SYSTEM privileges. This can be exploited to spawn an elevated command prompt, enabling full privilege escalation. |
| A denial-of-service security issue exists in the affected product and version. The security issue stems from a high number of requests sent to the web server. This could result in a web server crash however; this does not impact I/O control or communication . A power cycle is required to recover and utilize the webpage. |
| A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault. |
| A security issue exists within the Studio 5000 Logix Designer add-on profile (AOP) for the ArmorStart Classic distributed motor controller, resulting in denial-of-service. This vulnerability is possible due to the input of invalid values into Component Object Model (COM) methods. |
| A denial-of-service security issue exists in the affected product and version. The security issue is caused through CIP communication using crafted payloads. The security issue could result in no CIP communication with 1715 EtherNet/IP Adapter.A restart is required to recover. |
| A security issue exists within DataMosaix™ Private Cloud allowing for Persistent XSS. This vulnerability can result in the execution of malicious JavaScript, allowing for account takeover, credential theft, or redirection to a malicious website. |
| A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault. |
| A security issue was discovered within the legacy Ansible playbook component of Verve Asset Manager, caused by plaintext secrets incorrectly stored when a playbook is running. This component has been retired and has been optional since the 1.36 release in 2024. |
| A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. |
| A security issue exists within DataMosaix™ Private Cloud, allowing attackers to bypass MFA during setup and obtain a valid login-token cookie without knowing the users password. This vulnerability occurs when MFA is enabled but not completed within a 7-day period. |
| A security issue exists due to the web-based debugger agent enabled on Rockwell Automation ControlLogix® Ethernet Modules. If a specific IP address is used to connect to the WDB agent, it can allow remote attackers to perform memory dumps, modify memory, and control execution flow. |
| A Local Privilege Escalation vulnerability exists in the affected product. The vulnerability requires a local, low privileged threat actor to replace certain files during update and exists due to a failure to perform proper security checks before installation. |
| A security issue affecting multiple Cisco devices also directly impacts Stratix® 5410, 5700, and 8000 devices. This can lead to remote code execution by uploading and running malicious configurations without authentication. |
| Multiple denial-of-service vulnerabilities exist in the affected product. These issues can be triggered through various crafted inputs, including malformed Class 3 messages, memory leak conditions, and other resource exhaustion scenarios. Exploitation may cause the device to become unresponsive and, in some cases, result in a major nonrecoverable fault. Recovery may require a restart. |
| An improper authorization vulnerability exists in the Rockwell Automation affected products that could allow an unauthorized user to sign in. While removal of all role mappings is unlikely, it could occur in the case of unexpected or accidental removal by the administrator. If exploited, an unauthorized user could access data they previously but should no longer have access to. |
| A security issue was discovered in DataMosaix Private Cloud, allowing users with low privilege to perform sensitive database operations through exposed API endpoints. |
| A security issue exists within 432ES-IG3 Series A, which affects GuardLink® EtherNet/IP Interface, resulting in denial-of-service. A manual power cycle is required to recover the device. |
| Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. |